Why one property’s pipes matter to every Tulare tap
The City of Tulare uses groundwater as its sole water supply source, pumped from the Kaweah Subbasin, which the State’s Department of Water Resources has designated critically overdrafted. The City holds no federal project entitlements or other surface water rights. The surface water it does buy, from Tulare Irrigation District, is used only to recharge the aquifer; in 2020 that came to 2,344 million gallons. The City also holds a 75 percent contractual interest in the Swall recharge basin, which sits upgradient, so the City believes that recharged water flows toward its own wells.
So every glass from a City tap is pumped groundwater that the City works to put back. A backflow event does not reach that aquifer. It reaches the mains, pushing water from a private system backward toward the neighbors. That happens two ways. Backsiphonage occurs when street pressure suddenly drops, from a main break or heavy hydrant use, and a hose in a bucket, a sprinkler line in wet soil or a boiler loop gets pulled backward. Backpressure occurs when something on the property, a pump, a well or a pressurized tank, pushes harder than the street does. A backflow preventer is a one-way barrier designed and tested for those moments.
Picking the device by hazard
The assembly follows from what could flow back and which direction the force comes from. The cross-connection section of the California Plumbing Code (Section 603) sets out which devices may protect which hazards. In practice it looks like this:
| Device |
Stops backsiphonage |
Stops backpressure |
Typical use |
| Air gap |
Yes |
Yes |
Tank fills, equipment drains |
| Reduced pressure principle assembly (RP) |
Yes |
Yes |
Well premises at the meter, chemical injection, boilers with additives |
| Double check valve assembly |
Yes |
Yes, low hazard only |
Some fire and irrigation services |
| Pressure vacuum breaker |
Yes |
No |
Lawn irrigation set above the highest head |
| Hose bib vacuum breaker |
Yes |
No |
A single outdoor faucet |
Two mistakes come up repeatedly. One is protecting a high-hazard line, such as a sprinkler system with a fertilizer injector, with a device rated only for low hazard. The other is setting a pressure vacuum breaker lower than the heads on a sloped yard, where the water above it can drain back through. If your sprinklers are part of the job, we often pair the install with a look at the irrigation lines themselves.
The old well beside the house
This is the most Tulare-specific installation we do. The well ordinance, Municipal Code Chapter 7.09, requires a City-approved reduced pressure principle device at the public water supply meter connection for any premises with an auxiliary water supply, and a test at least once a year at the water user’s expense. The rule is about the premises having a well, not about whether the well is piped into the house.
The same chapter limits what can happen to the well. No construction permit is issued for property connected to the City system, inside city limits or within 500 feet of a feasible connection point, and modifications other than abandonment or destruction are barred in those areas. Any of that work needs a permit from the Public Works Director, and a well left a year without maintenance or use counts as abandoned.
That leaves an owner two real paths: keep the well and protect the meter with an RP, or take the well through the City’s abandonment or destruction permit. Ask the Water Division whether the second path ends the RP requirement on your parcel before you commit to either.
Setting an RP at the meter
An RP is the most demanding of these devices to place well:
- Above grade. Never in a pit or below-grade box where its relief port could be submerged.
- A path for discharge. An RP can release a lot of water when it does its job. It goes where that water drains away from the foundation, the walkway and the neighbor’s lot.
- Room to test. Shutoffs on both sides, test cocks facing out, and space for a tester’s hands and gauge.
- Protection. A ventilated, draining enclosure guards against impact, sun and the occasional cold night without trapping water around the body.
- Thermal expansion. Once the assembly is in, heated water can no longer push back toward the street. A properly sized expansion tank at the heater absorbs that volume so the relief valve does not have to; it is a standard part of a well-planned meter install, and we set it up alongside any water heater replacement if one is due anyway.
From install day into the yearly cycle
A new assembly is tested as it goes into service. From then on it belongs to the City’s annual program: Tulare requires every business or residential property with a backflow assembly to have it tested each year, accepts results only from testers certified through ABPA or the CA-NV Section of AWWA with calibration on file at the Water Division, wants forms in blue ink, and may disconnect devices not tested and submitted on time. Keep the make, model, size and serial number with your property papers. The obligation stays with the premises, so the next owner inherits both the device and its due date. For what test day looks like, see our page on annual backflow certification.