A backflow preventer is a category, not a part number
When a notice, an inspector or a fire protection contractor tells you to “install a backflow preventer,” it sounds like one item you could grab at a supply house. It is not. Several assembly types exist, built very differently, and they do not offer the same protection. Put the wrong one on a connection and it may pass every test while still being the wrong device for the risk it faces.
The right choice comes from one question: what could flow backward from your property into the City’s water, and how harmful would it be? Lawn water with nothing added is a different risk from a sprinkler system that injects fertilizer, a commercial boiler dosed with treatment chemicals, or a fire line with a pumper connection. Working that out is the survey, and it happens before anyone talks about brands or sizes.
The ranking written into Exeter’s code
Exeter’s backflow chapter names three kinds of protection, strongest first.
Air gap (AG). A physical, open-air break between the supply outlet and whatever receives the water. Nothing can siphon across empty air, so it protects best of all. It also gives up line pressure at that point, so it suits tanks and process equipment more than a pressurized household line.
Reduced pressure principle (RP). Two independent check valves with a relief valve between them that opens to atmosphere if either check leaks. This is the assembly for connections where backflow could carry something that makes people sick, such as chemical injection or certain commercial and process connections.
Double check (DC). Two independent check valves and no relief valve. It guards against pollutants that spoil taste, color or smell but are not a health hazard. It is more compact and costs less pressure, but it is no substitute for an RP on a health hazard.
Whatever the type, Exeter requires an assembly approved by the USC Foundation, which evaluates designs in the laboratory and in the field before listing them. The same chapter requires an approved device on fire protection services. Inside the home, the plumbing code has its own smaller devices, such as vacuum breakers on hose bibs, but those are separate from the assembly that shields the City’s system.
Your side of the meter, your assembly
Under Exeter’s water service rules, the City’s responsibility ends at the meter. When the City needs a protective device to safeguard its system, section 13.08.120 says the consumer installs it immediately, at the consumer’s expense, on the property side. The backflow chapter says the same about assemblies, which are installed by and at the expense of the water user.
So the assembly is yours to buy, own and maintain, and its first test is due the day it goes in. After that it needs a yearly backflow test in Exeter, plus another after any repair or relocation.
Replacing an existing assembly follows the same path. If yours has failed a test and the body is cracked or the parts are gone, we first check whether the hazard behind it has changed since it went in. A property that has added a fertilizer injector or a booster pump may now need an RP where a double check once sat, and the replacement is the right moment to correct that.
Details that decide whether an install works
A handful of decisions matter more than the brand cast into the body.
- Location and drainage. An RP relief port can release a lot of water during a failure. It goes above grade, never in a pit that can flood, with a clear path for that water to drain away from the building.
- Orientation. Assemblies are approved for specific orientations, horizontal or vertical. One mounted outside its approval is no longer an approved installation.
- Room to test. Test cocks and shutoffs need to face where a tester can reach them, with space to work.
- Pressure loss. Water loses pressure passing the checks, more through an RP. The City puts normal household pressure at an average of 35 to 50 psi, so we size the assembly to leave usable pressure at your farthest fixture. If pressure is already marginal, fixing low water pressure may need to come first.
- Thermal expansion. Once water cannot retreat to the street, heated water expands into a closed system. An expansion tank sized to your heater keeps the relief valve from weeping.
When the connection reaches the sidewalk or street
Most installs happen entirely on private property. When one does not, for example a new fire service or a larger line tied in within the public right-of-way, Exeter’s street-cut rules apply. A written encroachment permit is required before cutting any City street, alley or sidewalk, obtained at least 24 hours ahead, and the excavation may not stay open longer than 48 hours unless the city engineer extends it. Those permits go only to state-licensed contractors or public utilities, and the City’s encroachment application even carries a checkbox for backflow work. We plan the trench and the assembly so the right-of-way portion fits inside that window.